Chapter 4 Operation of the Server 4-23
Command operation
1. Use the showdualpowerfeed(8) command to display the current setting status of
the dual power feed.
2. Use the setdualpowerfeed(8) command to enable or disable the dual power feed
of this system.
3. Confirm the new setting, and if it is correct, turn off the input power and then turn
on to apply the specified configuration. When you enabled the dual power feed
mode, you can apply the configuration by executing the rebootxscf(8) command.
4. Confirm whether the setting is valid after turning off/on the input power.
XSCF> showdualpowerfeed
Dual power feed is disabled.
<Example 1> Enabling the dual power feed.
XSCF> setdualpowerfeed -s enable
disable -> enable
NOTE: Dual power feed will be enabled the next time the platform
is powered on.
<Example 2> Disabling the dual power feed.
XSCF> setdualpowerfeed -s disable
enable -> disable
NOTE: Dual power feed will be disabled the next time the platform
is powered on.
XSCF> showdualpowerfeed
disable -> enable
NOTE: Dual power feed will be enabled the next time the platform
is powered on.
XSCF> showdualpowerfeed
Dual power feed is enabled.