Chapter 2 Setting Up XSCF 2-185
2.2.17 Altitude Administration
This section explains the altitude settings. The server changes the system monitoring due to
the altitude of the server. Therefore, the operator must set the altitude during the initial
system setting. This setting is done by FEs.
With the altitude setting, the fan speed level varies by the environmental temperature. To
display the fan speed level for each environmental temperature, execute the
showenvironment(8) command. For the fan speed level corresponding to the altitude and
the environmental temperature, see Section 4.1.1, “Displaying System Information” on
page 4-2.
TABLE 2-36 lists setting items and the corresponding shell commands.
Setting Altitude
Command operation
1. Use the showaltitude(8) command to check the current altitude settings.
2. Use the setaltitude(8) command to set the altitude settings.
Note – To apply the specified configuration, execute the rebootxscf(8) command and
reset XSCF.
TABLE 2-36 Altitude Administration
Item Description Shell Command Remarks
Display settings Display the altitude settings for the server. showaltitude
Altitude Specify the location altitude of the server:
A set unit is specified in increments of 100 meters. The
setting of less than 100 meters is rounded up.
setaltitude A negative altitude
cannot be set.
XSCF> showaltitude
1000m
<Example 1> Specify an altitude of 1000 meters
XSCF> setaltitude -s altitude=1000
1000m
<Example 2> Specify an altitude of 200 meters
XSCF> setaltitude -s altitude=200
200m