46
Code Description
ULMCIM Mini Single Channel Input Unit (recognised as input unit)
ULMCIM-C Mini Single Channel Input Unit (recognised as callpoint)
ULBU Mini Module Box Unit (Empty box)
Product Codes
Note:
1. The end of line resistor provided must always
be fitted, even if the input is unused.
2. Monitored inputs can detect open or short
circuit faults.
3. Recommended loop cable type: FIRETUF,
FP200, MICC.
Installation
1. Fit the box in position using the mounting details
below.
2. Connect the unit according to the diagram below.
3. ULMCIM & ULMCIM-S module can be fitted inside
a junction box.
4. Up to 3 ULMCIM & ULMCIM-C modules can be
fitted inside the FIBOX, as per diagram below.
Note:
No addressing of the interface is required.
(See control panel operation for details).
This needs to be programmed as a callpoint on site
installed PC software.
Standard Connections
Technical Specification
Operation
Normal Standby, Alarm, NAC Silenced, Alarm Reset, Trouble, Supervisory, Drill
Code ULMCIM and ULMCIM-C
Description Single Channel Input Units
Standards UL864 9
th
edition
Signalling Line Circuit
Style 7, Class A, Supervised, Power Limited
Current 332 µA
Operating Voltage 24 V dc
Input
Initiating Circuit Class B, Style C, Supervised, Power Limited
Voltage (8.4 Vpp every 1 second) 8.4 V dc
Current 1.2 mA
Trigger Resistance 5.6 k
End Of Line Resistor 22 k
Line Impendance 16 (max)
Environmental
Operating Temperature 0°C to 49°C
Humidity (Non Condensing) 0 to 93 %RH
Physical
Dimensions (H x W x D) 65mm x 35mm x 18.5mm
Weight >0.1kg
Ingress Protection IP40
Compatibility
Suitable for use with Menvier analogue addressable fire systems
Description SLC Field Wiring Circuit (input) Single Channel Input
Wiring Gauge 12 Max AWG 12 Max AWG
Wiring Class Class A Style 7 Class B Style C
Ground Fault Impedance 0.1 ohm 0.1 ohm
Supervised, Power Limited Yes Yes
Dimensions
2 self tapping screws.